Calculate NEC 690.8 compliant DC fuse ratings for PV string circuits.
Multiply the panel's Isc by 1.56 per NEC 690.8(B) for continuous loads, apply cold-temperature correction, then round up to the next standard fuse rating.
NEC 690.9 requires fuses on each string when three or more strings are in parallel. With two strings, fuses are required only if backfeed current exceeds the panel's max series OCPD rating.
The panel nameplate specifies the 'Max Series Overcurrent Device Rating' — typically 15A–20A for residential modules, 30A–60A for commercial ones. Never exceed this value.